240W/48V Industrial DIN Rail Power Supply
240W/48V Industrial Din Rail Power Supply
GWS-DP240-48 is one economical slim 240W industrial DIN Rail power supply series, adapting to be installed on TS-35/7.5 or TS-35/15 mounting rails. The entire series adopts the full range AC input from 90VAC to 264VAC and conforms to EN61000-3-2, the norm the European Union regulates for harmonic current.
GWS-DP240-48 is designed with a metal shell, which is easy to increase the heat dissipation of the machine. The working efficiency is as high as 90%. The product can work in -40℃ to 70℃ambient temperature under the condition of air circulation. It has a constant current mode overload protection function and is suitable for various Inductive or capacitive load applications, complete protection functions and compliance with industrial control equipment certifications, making GWS-DP240-48 a very competitive power solution for industrial applications.

| Porduct Name | 240W/48V Industrial DIN Rail Power Supply |
| Model | GWS-DP240-48 |
| Group of Output | 1 |
| DC Voltage | DC48V |
| Default Output Voltage | 48.00-48.2V (VIN: 220VAC / LOAD: 0A) |
| Output Rated Current | 5A |
| Output Current Range | 0-5A |
| Output Rated Power | 240W |
| Total Peak Output Power | Up to 360W(Sustainable time 10S/220VAC) |
| Peak Output Current | 7.5A( Sustainable time 10S/220VAC) |
| Ripple Noise | Peak - Peak ≤100mV (Test Method: The terminal shall be in parallel with capacitance of 0.1uF and 47uF, testing at 20MHz) |
| Output Regulation Range | 47~56V |
| Stabilized Voltage Precision | ±1% (@ 90V-264Vac input, 100% load) |
| Line Regulation | ±0.5% (@ 90-264Vac input, 100% load) |
| Load Regulation | ±1% (@ 90-264Vac input, 0-100% load) |
| Output Start Time | < 2S @ nominal input (100% load ) |
| Output Hold Time | > 20ms @ 115Vac, > 115 ms @ 230Vac (100% load ) |
| Voltage Overshoot | ≤5% |
| Input Voltage Range | 90~264VAC |
| Input Rated Voltage Range | 100~240VAC |
| Frequency Range | 47~63Hz |
| Rated Frequency | 50/60Hz |
| Starting Voltage | 90VAC |
| Efficiency | > 90.0% @ 115VAC, > 91.0% @ 230VAC |
| Input Current @25℃ | < 4.40A @ 115VAC, < 2.20A @ 230VAC |
| Inrush Starting Current @25℃ | < 35A @ 115VAC& 230VAC |
| Power Factor | > 0.99 @ 115VAC, > 0.93 @ 230VAC |
| Over Power Protection | 288~360W Swing machine (Testing method: Increase the output current until enabling the protection. Protection mode:Swing machine, Self-recovery after over-power released.) |
| Over Voltage Protection | 57~70V Swing machine (Short circuit the Pin1-2 of U8, swing machine. Output recovery to normal after removing the short circuit) Note: Do not use external voltage. |
| Over Current Protection | 6~7.5A Swing machine (Testing method: Increase the output current until enabling the protection. Protection mode:Swing machine, Self-recovery after over-current released.) |
| Short Circuit Protection | It achieves the long-term short circuit by connecting a sufficient cross-sectional area copper cable (Length at 15cm±5cm) with power output port. Self-recovery to normal after removing the short circuit. |
| Operation Temperature and Humidity | -40~70℃; 20%~95%RH |
| Storage Temperature and Humidity | -40℃~85℃; 10%~95%RH non-condensing |
| Temperature Coefficient | ±0.03%/℃(0~50℃) |
| Libration | Frequency range: 10 ~ 500Hz, Acceleration: 2G, Each sweep cycle 10min. Six sweeps along the X, Y, and Z axis |
| Surge | Acceleration: 20G, Duration time: 11mS, Three shocks along X, Y and Z axis |
| Altitude | 2000m |
| Security Standard | GB4943/EN60950 ■Reference □Certification |
| Dielectric Strength | Input—Output:3KVac/10mA; Input--Case:1.5KVac/10mA; Output---Case:0.5KVDC/10mA Time for each testing is 1min. |
| Grounding Test | Test Condition: 32A/2min; Ground bond: <0.1 ohms. |
| Leakage Current @25℃ | Input to GND ≤3.5mA; Input to output ≤0.25mA (Input 264Vac, 63Hz) |
| Insulation Resistance | Input—Output: 10M ohms |
| Conducted Interference | EN55022, EN55024, FCC PART 15 CLASS B |
| Radiated Interference | EN55022, EN55024, FCC PART 15 CLASS B |
| Harmaonic current | EN61000-3-2 CLASS D |
| Conducted Emission | EN61000-4-6 Level3 |
| Radiated Emission | EN61000-4-3 Leve3 criterion B |
| Power Frequency Emission | EN61000-4-8 Level3 |
| Electrostatic Emission | EN61000-4-2 Level4 criterion B |
| EFT | EN61000-4-4 Level4 criterion B |
| Surge | EN61000-4-5 Level4 criterion B |
| Dip and Interruption | EN61000-4-11 |