Name:120W/12V Industrial DIN Rail Power Supply

Model:GWS-DP120-12

120W/12V Industrial DIN Rail Power Supply

Name:
Information:
Email:
Telephone:
Company:
Code:

  Submit
  • Overview

  • Specification

  • Download

120W/12V Industrial DIN Rail Power Supply


GWS-DP120-12 is one economical slim 120W  industrial DIN Rail power supply series, adapting to be installed on TS-35/7.5 or TS-35/15 mounting rails. The entire series adopts the full range AC input from 90VAC-264VAC or 110-230VAC (Custom) and conforms to EN61000-3-2, the norm the European Union regulates for harmonic current.

GWS-DP120-12 is designed with metal housing that enhances the unit’s power dissipation. With working efficiency up to 90%, the entire series can operate at the ambient temperature between -40℃ to 70℃ under air convection. It is equipped with constant current mode for over load protection, fitting various inductive or capacitive applications. The complete protection functions and relevant certificates for industrial control apparatus make GWS-DP120-12 a very competitive power supply solution for industrial applications.


Product Name120W/12V Industrial DIN Rail Power Supply
ModelGWS-DP120-12
Group Of Output 1
DC Voltage 12VDC
Default Output Voltage 0-10A
Ripple Noise0<Ta≤55℃,≤50mVp-p;-15≤Ta≤0℃,≤100mVp-p
Stabilized Voltage Precision ±1%
Line Regulation ±1%
Load Regulation ±1%
Temperature Coefficient ±0.03%/℃
Output Start Time ≤3.0S (120Vac input, Full load); ≤2.0S (220Vac input, Full load)
Output Hold Time ≥10mS(120Vac input, Full load); ≥20mS(220Vac input, Full load)
Voltage Overshoot <5.0%
Input Voltage Range 90VAC~264VAC or 110~230VAC (Custom)
Input Rated Voltage Range 100VAC~240VAC or 110~230VAC (Custom)
Frequency Range 47Hz~63Hz or 50Hz~60Hz (Custom)
Efficiency 90%
Input Current <1A
Inrush Starting Current <40A@300Vac Cold start
Leakage Current input to output less than 0.25mA
Over Power Protection144~180W Swing machine (Testing method: Increase the output current until enabling the protection. Protection mode:Swing machine, Self-recovery after over-power released.)
Over Voltage Protection15-16V Swing machine (Short circuit the Pin1-2 of U8, swing machine. Output recovery to normal after removing the short circuit) Note: Do not use external voltage.
Over Current Protection12~15A Swing machine (Testing method: Increase the output current until enabling the protection. Protection mode:Swing machine, Self-recovery after over-current released.)
Short Circuit ProtectionIt can be short circuited for a long time and automatically recover after the short circuit is eliminated.
Operation Temperature And Humidity-40℃~70℃; 20%~90%RH No condensing
Storage Temperature And Humidity -40℃~85℃; 5%~95%RH No condensing
Security Standard GB4943/EN62368-1
Dielectric Strength Input—Output:3KVac/10mA; Input--Case:1.5KVac/10mA; Output---Case:0.5KVDC/10mA Time for each testing is 1min.
Insulation Resistance Input-Output: 100M ohms; Input-Case: 100M ohms; Output-Case: 100M ohms;
Electromagnetic Interference EN55022 Class A
Harmaonic Current IEC61000-3-2 class A equipment requirements
Electromagnetic interference Immunity EN61000-4-2,4,5,6,8,11 ENV50204, class A heavy industry standard
Design MTBF 100,000Hrs AT 25℃, MIL-217 Method 2 Components Stress Method
NotesIf the specification is not specified, all specifications and parameters shall be measured at rated input, rated load and 25 C ambient temperature. Ripple noise test method: the use of a 12# twisted pair, while the terminal to parallel capacitance of 0.1uF and 10uF, measured at the scope of the oscilloscope 20MHz bandwidth. The power supply will be installed on the final equipment as a component, and the final equipment will still have to meet the EMC condition.